3−28
Additional Analog Input Settings
Input Range Settings – The parameters in the following table adjust the input
characteristics of the analog current input. When using the inputs to command the
inverter output frequency, these parameters adjust the starting and ending ranges for
the current, as well as the output frequency range. Related characteristic diagrams are
located in "
Analog sampling setting is the value specified in A016.
Func.
Code
A101
A102
A103
A104
A105
Refer to parameter A011 to A015 for analog voltage input.
NOTE: You cannot give voltage input and current input ([O] and [OI] input) at the same
time on X200 series inverter.
More user manuals on
Analog Input Settings " on page 3-13.
"A" Function
Name /
SRW Display
[OI]-[L] input active range
start frequency
OI-EXS
0000.0Hz
[OI]-[L] input active range
end frequency
OI-EXE
0000.0Hz
[OI]-[L] input active range
start current
OI-EX%S
00000%
[OI]-[L] input active range
end voltage
OI-EX%E
00000%
[OI]-[L] input start frequency
enable
OI-LVL
0Hz
ManualsBase.com
Description
The output frequency
corresponding to the analog input
range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the
current input range,
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A101 value)
01...Use 0Hz
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
0.0
0.0
Hz
0.0
0.0
Hz
0.
0.
%
100.
100.
%
01
01