Func.
Code
B052
B053
(high)
B053
(low)
B054
B055
B056
B080
B082
B083
B084
B085
More user manuals on
Name
R/W
OV-LAD Stop level of
R/W Setting the OV-LAD stop level of
non stop operation
setting
Deceleration time of
R/W
non stop operation
setting
R/W
Frequency width of
R/W Setting of the first quick
quick deceleration
setting
DC bus AVR P-gain
R/W Proportional gain adjustment for
DC bus AVR I-time
R/W Integration time adjustment for
[AM]analog signal gain R/W Adjust of analog output at
Start frequency
R/W Sets the starting frequency for
adjustment
Carrier frequency
R/W Sets the PWM carrier (internal
setting
Initialization mode
R/W Select the type of initialization to
(parameters or trip
history)
Country for
R/W Select default parameter values
initialization
ManualsBase.com
List of Holding Registers
Description
non stop operation. Range is 0.0
to 1000.0
Range is 0.01 to 3000
deceleration width. Range is 0.0
to 10.0
DC bus AVR function. Range is:
0.2 to 5.0
DC bus AVR function. Range is:
0.0 to 150.0
terminal [AM],
range is 0 to 255
the inverter output, range is 0.5
to 9.9 Hz
switching frequency), range is
2.0 to 12.0 kHz
occur, three option codes:
00...Trip history clear
01...Parameter initialization
02... Trip history clear and
parameter initialization
for country on initialization,
three option codes:
00...Japan
01...Europe
02...US
B−33
Network Data
Reg.
Range
Res.
10CBh 0 to 10000
0.1 V
10CCh
1 to 300000 0.01 sec
10CDh
10CEh
0 to 100
0.1 Hz
1173h
2 to 50
0.1
1174h
0 to 1500
0.1s
10CFh
0 to 255
10D1h
5 to 99
0.1 Hz
10D2h
20 to 120
0.1 Hz
10D3h
0, 1, 2
10D4h

Advertisement

Table of Contents
loading