Run Command Source Setting – For parameter A002, the following table provides a
further description of each option, and a reference to other page(s) for more information.
A001/A002 Override Sources – The inverter allows some sources to override the setting
for output frequency and Run command in A001 and A002. this provides flexibility for
applications that occasionally need to use a different source, leaving the standard
settings in A001/A002.
The inverter has other control sources that can temporarily override the parameter
A001 setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority ("1" is the highest priority).
The inverter also has other control sources that can temporarily override the parameter
A002 setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority ("1" is the highest priority).
More user manuals on
Code
01
Control terminal – The [FW] or [RV] input terminals control
Run/Stop operation
02
Keypad Run key – The Run and Stop keys provide control
03
ModBus network input – The network has a dedicated coil
for Run/Stop command and a coil for FW/RV
Priority
A001 Frequency Source Setting Method
1
[CF1] to [CF4] Multi-speed terminals
2
[OPE] Operator Control intelligent input
3
[F-TM] intelligent input
4
[AT] terminal
5
A001 Frequency source setting
Priority
A002 Run Command Setting Method
1
[OPE] Operator Control intelligent input
2
[F-TM] intelligent input
3
A002 Run command source setting
ManualsBase.com
Run Command Source
3−11
Refer to page(s)...
4-11
2-24
B-19
Refer to page...
4-12
4-29
4-31
4-22
3-10
Refer to page...
4-29
4-31
3-10