Machine automation controller, cj / nj-series, ethercat slave unit, cpu unit
Hide thumbs Also See for CJ1W-ECT21:
Table of Contents

Advertisement

2
Set the I/O Communication Area Setting Table on the Edit Special Unit Settings Tab Page.
3
Establish communications with the NJ-series Controller and go online. Download the
CPU/Expansion Rack configuration and settings for the EtherCAT Slave Unit. Use the synchro-
nization operation of the Sysmac Studio to download the data.
Clear the selection of the following (all items are not transferred).
• CJ-series Special Unit parameters and EtherCAT slave backup parameters.
• Slave Terminal Unit operation settings and NX Unit application data.
After downloading the settings, the EtherCAT Slave Unit will automatically restart to enable the
settings.
4
Check the indicators on the EtherCAT Slave Unit.
If the RUN indicator is lit while the ERC and ERH indicators are not lit, it indicates that the Ether-
CAT Slave Unit has recognized the new I/O communication area settings. Refer to Setting
Results Codes on page 3-23.
CJ-series EtherCAT Slave Units Operation Manual for NJ-series CPU Unit (W542)