Omron CJ1W-ECT21 Operation Manual page 132

Machine automation controller, cj / nj-series, ethercat slave unit, cpu unit
Hide thumbs Also See for CJ1W-ECT21:
Table of Contents

Advertisement

5 Troubleshooting
Event name
Sll Unit Verification Error
Meaning
An error occurred in Slave Unit verification.
Source
PLC Function Module
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
An error occurred in Slave Unit
information.
Attached
None
information
Precautions/
None
Remarks
Event name
I/O Refresh Error
Meaning
The I/O memory in the destination CPU Unit for I/O refreshing could not be found when refreshing in the
CPU Unit.
Source
PLC Function Module
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The data area type, data area size
and first word in the data area
were outside of the specified
range.
I/O words are allocated in an EM
bank that does not exist.
Attached
None
information
Precautions/
None
Remarks
5 - 22
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Replace the EtherCAT Slave Unit. None
Source details
Minor fault
Recovery
Continues.
Operation
Data type
---
Correction
Correct the I/O allocations so that
the data area type, data area size
and first word in the data area are
allocated within the specified
range.
Correct the I/O allocations so that
only I/O words that exist in the I/O
memory of a CPU Unit are allo-
cated.
CJ-series EtherCAT Slave Units Operation Manual for NJ-series CPU Unit (W542)
Event code
05420000 hex
CJ-series Unit
Detection
timing
Cycle the power
Log category
supply
The EtherCAT communications stops in Init state.
Name
---
Prevention
Event code
35680000 hex
CJ-series Unit
Detection
timing
Automatic
Log category
recovery
The EtherCAT communications stops in Init state.
Name
---
Prevention
Allocate the data area type, data
area size and first word in the data
area within the specified range.
Allocate only I/O words that exist
in the I/O memory of a CPU Unit.
At power ON or
Controller reset
System
At power ON or
Controller reset
System

Advertisement

Table of Contents
loading

Table of Contents