Omron CJ1W-ECT21 Operation Manual page 120

Machine automation controller, cj / nj-series, ethercat slave unit, cpu unit
Hide thumbs Also See for CJ1W-ECT21:
Table of Contents

Advertisement

5 Troubleshooting
Indicator
ECAT
ECAT
ERC
ERH
RUN
ERR
*1
*1
Not
Lit
B
B
Lit
*1. If the EtherCAT master requests transition to Safe-Operational state or Operational state, the Unit remains in the Pre-Op-
erational state, the ECAT ERR and ECAT RUN indicators are blinking.
*2. If the EtherCAT master requests transition to Safe-Operational state or Operational state, the Unit remains in the Pre-Op-
erational state, and the device variable *_AlStatusErr is TRUE.
5 - 10
Error
Cause
RUN
---
CPU Unit
A major fault
Major Fault
occurred in the CPU
Unit.
CPU Unit
An error occurred in
Watchdog
the CPU Unit.
Timer Error
CPU Unit
Servicing from the
Service
CPU Unit was not
Monitoring
completed within the
Error
fixed interval.
The monitoring time
is normally 11 s.
An error occurred
while exchanging
data with the CPU
Unit.
I/O Bus
An error occurred
Error
while exchanging
data with the CPU
Unit.
I/O Refresh
The I/O communica-
Error
tion area does not
exist in the CPU
Unit.
This can occur when
the I/O communica-
tion area is set incor-
rectly, when the Unit
is mounted to a dif-
ferent CPU Unit with
a different number of
EM banks or when
EM has been con-
verted to file mem-
ory.
CJ-series EtherCAT Slave Units Operation Manual for NJ-series CPU Unit (W542)
Status of
Error
device vari-
Unit opera-
log
ables for
tion
(hex)
CJ-series
Units
An emer-
---
*_AlStatusEr
gency code
r (Slave AL
is sent if
Status Error)
EtherCAT
is TRUE.
Slave Unit
is in
Pre-Opera-
tional state.
An emer-
0001
gency code
is sent if
EtherCAT
0002
Slave Unit
is in
Pre-Opera-
tional state
and records
the error in
the error
log.
000E
---
0347
*_IORefErr
(I/O Refresh
Error) is
*2
TRUE.
Countermeasures
Clear the cause of
the error and then
restart the CPU
*2
Unit.
Replace the CPU
Unit.
Check and correct
the CPU Unit's
operating environ-
ment.
Check and correct
the CPU Unit's
operating environ-
ment and then
cycle power to the
CPU Unit.
Check the I/O com-
munication area
and change to the
correct allocation
and restart the
EtherCAT Slave
Unit.