13.5 Configuring the Modem

The modem must be programmed with the Call Out telephone numbers in order to
operate the Remote Notification option.
To configure the modem, connect the serial port of a standard PC computer to
the modem through the serial cable. Run a terminal emulation program on the
computer. Test the connection to the modem by typing [A], [T] and [ENTER].
The modem should respond with either "OK" or "0" (zero). If the modem does not
respond, consult the modem manufacturer's manual to confirm your setup. If the
modem still does not respond, then seek technical assistance from your modem
manufacturer.
After connection, perform "Basic Modem Configuration" and the remaining
sections of this chapter.

13.5.1 Basic Modem Configuration

The basic modem should be a plug and play type. All setup is done by the UPS.
Only the initial phone number needs to be entered by the user.

13.5.2 Configuring the Modem to Call a Remote Computer

To configure the modem to call a remote computer, perform the following
procedure:
NOTE: The brackets ([ ]) in the following steps indicate characters that require
keying in prior to pressing [ENTER].
1. Connect the modem to the PC through the serial port as described in the modem
manufacturer's manual .
2. Key in [A], [T], then press [ENTER].
3. Confirm that the modem responds with "OK" or "0" (zero).
NOTE: In steps 4 through 7, the "xxxxxxx" is the phone number of a remote
computer. The phone number should include all local line and long
distance access numbers needed to dial out. This number is limited to 32
characters. For example, use "9" if needed for an outside line, "1" for long
distance + (Area Code) + Number or whatever access codes are needed to
dial the call directly. Add a "," in the number anywhere that a delay is
needed. This will cause a two-second delay. More than one delay may be
added to the number; for example, enter "AT&Z0=T,9,,1 (Area Code) (Phone
Number)".
4. To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [xxxxxxx],
then press [ENTER].
5. To program a group two number, key in [A], [T], [&], [Z], [1], [=], [xxxxxxx], then
press [ENTER].
6. To program a group three number, key in [A], [T], [&], [Z], [2], [=], [xxxxxxx], then
press [ENTER].
13--6
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 REV. G 061502