DC Power Requirements
The installation site must meet the following DC power requirements:
•
Nominal -48 VDC; range: -37 VDC to -56 VDC; 1.5 kW maximum
•
DC current: 31 A at -48 VDC
296-1011-200 Rel. 5.0, Doc. Rev. 08.01
Caution: Input DC voltage must not exceed -72 VDC.
Plastic Fascia Chassis Technical Specifications
Power Specifications
A-21