Omron E5CN-H Communications Manual page 56

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

Variable
Address
Parameter name
type
C3 (83)
0016
Event Input Assignment 1 (See note 1.) H'00000000 (0): None
C3 (83)
0017
Event Input Assignment 2 (See note 2.) H'00000000 to H'0000000A (0 to 10)
C3 (83)
0018
Event Input Assignment 3 (See note 3.) H'00000000 to H'0000000A (0 to 10)
C3 (83)
0019
Event Input Assignment 4 (See note 4.) H'00000000 to H'0000000A (0 to 10)
C3 (83)
001B
SP Ramp Time Unit
C3 (83)
001D
Standby Sequence Reset
C3 (83)
001E
Auxiliary Output 1 Open in Alarm
C3 (83)
001F
Alarm 1 Hysteresis
Note 1:
For Controllers with two event inputs (events 1 and 2), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 0.
Note 2:
For Controllers with two event inputs (events 1 and 2), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 1.
Note 3:
For Controllers with two event inputs (events 3 and 4), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 0.
Note 4:
For Controllers with two event inputs (events 3 and 4), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 1.
Note 5:
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000001 (1): RUN/STOP
H'00000002 (2): Auto/manual switch
H'00000003 (3): Program Start (See note 5.)
H'00000004 (4): Direct/reverse operation
H'00000005 (5): SP mode change
H'00000006 (6): 100% AT execute/cancel
H'00000007 (7): 40% AT execute/cancel
H'00000008 (8): Setting change enable/disable
H'00000009 (9): Communications writing enabled/disabled
H'0000000A (10): Alarm latch cancel
* Same as for Event Input Assignment 1.
* Same as for Event Input Assignment 1.
* Same as for Event Input Assignment 1.
H'00000000 (0): EU/second
H'00000001 (1): EU/minute
H'00000002 (2): EU/hour
H'00000000 (0): Condition A
H'00000001 (1): Condition B
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
Level
Initial
setting
Advanced
function
setting
Initial
setting
3-7