(4) Response Code
Normal Completion
Response code
0000
Normal completion
Error Occurred
Response code
Error name
1002
Command too
short
1101
Area type error
1103
Start address out-
of-range error
1104
End address out-
of-range error
1003
Number of ele-
ments/data mis-
match
1100
Parameter error
3003
Read-only error
2203
Operation error
Note:
For details on AT (auto-tuning), refer to the separate User's
Manuals.
(5) Precautions
● Alarm Function
Even though alarms are not displayed on the Controller's display, they
function normally in communications.
2.3 Detailed Description of the Services
Name
Description
No errors were found.
Cause
The command is too short.
The variable type is wrong.
Write start address is out of range.
The write end address (write start
address + number of elements)
exceeds the final address of the vari-
able area.
The number of data does not match
the number of elements.
• Bit position is not "00."
• The write data is out of the setting
range.
Variable type "C0" was written to.
• The Communications Writing
parameter is set to "OFF" (dis-
abled).
• Attempted to write to a parameter
in setup area 1 from setup area 0.
• Attempted to write to a protect
parameter from other than the pro-
tect level.
• AT (auto-tuning) was in progress.
(See note.)
• EEPROM error
2-11