Omron E5CN-H Communications Manual page 112

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

Address
Parameter name
Four-byte
Two-byte
mode
mode
1206
3203
Monitor/Setting Item 2
1208
3204
Monitor/Setting Item 3
120A
3205
Monitor/Setting Item 4
120C
3206
Monitor/Setting Item 5
1302
3301
SP Tracking
1304
3302
PID Set Automatic Selection
Data
1306
3303
PID Set Automatic Selection
Hysteresis
1308
3304
PV Dead Band
130A
3305
Cold Junction Compensation
Method
α
1314
330A
131E
330F
AT Calculated Gain
1320
3310
AT Hysteresis
1322
3311
Limit Cycle MV Amplitude
1328
3314
Heater Burnout Latch
132A
3315
Heater Burnout Hysteresis
132C
3316
HS Alarm Latch
132E
3317
HS Alarm Hysteresis
1334
331A
Bank Numbers Used
1338
331C
HB ON/OFF
133A
331D
MB Command Logic Switching
(See note 1.)
133C
331E
Input Error Output
133E
331F
Input Shift Type
1340
3320
MV at Stop and Error Addition
1342
3321
ST Stable Range
1344
3322
RT
1346
3323
HS Alarm Use
Note 1:
The logic of the Modbus Write Variable operation command is not affected.
6.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 to H'00000010 (0 to 16)
* Same as for Monitor/Setting Item 1.
H'00000000 to H'00000010 (0 to 16)
* Same as for Monitor/Setting Item 1.
H'00000000 to H'00000010 (0 to 16)
* Same as for Monitor/Setting Item 1.
H'00000000 to H'00000010 (0 to 16)
* Same as for Monitor/Setting Item 1.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): PV
H'00000001 (1): DV
H'00000002 (2): SP
H'0000000A to H'0000270F (0.10 to 99.99)
H'00000000 to H'00007E90 (0 to 32400)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 to H'00000064 (0.00 to 1.00)
H'00000001 to H'00000064 (0.1 to 10.0)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'000003E7 (0.01 to 9.99)
H'00000032 to H'000001F4 (5.0 to 50.0)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
H'00000000 (0): Disabled
H'00000001 (1): 2 Bank
H'00000002 (2): 4 Bank
H'00000003 (3): 8 Bank
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): Temperature input 1-point shift
H'00000001 (1): Temperature input 2-point shift
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'00007E90 (0.1 to 3240.0)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
Level
Advanced
function
setting
Initial
setting
Advanced
function
setting
6-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-hE5an-h

Table of Contents