Omron E5CN-H Communications Manual page 111

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

SECTION 6 Communications Data for Modbus
Address
Parameter name
Four-byte
Two-byte
mode
mode
1022
3011
PV Status Display Function
1024
3012
SV Status Display Function
1100
3100
Communications Protocol Set-
ting (See note 1.)
1102
3101
Communications Unit No.
(See note 1.)
1104
3102
Communications Baud Rate
(See note 1.)
1106
3103
Communications Data Length
(See note 1.)
1108
3104
Communications Stop Bits
(See note 1.)
110A
3105
Communications Parity
(See note 1.)
110C
3106
Send Data Wait Time
(See note 1.)
1200
3200
PF Setting
1204
3202
Monitor/Setting Item 1
Note 1:
After communications parameters have been changed, reset the Controller to enable them.
6-10
Setting (monitor) value
H'00000000 (0):OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 1 to 3 OR status
H'00000007 (7): Heater alarm
H'00000000 to H'00000007 (0 to 7)
* Same as for PV Status Display Function.
H'00000000 (0): CompoWay/F (SYSWAY)
H'00000001 (1): Modbus
H'00000000 to H'00000063 (0 to 99)
H'00000000 (0): 1.2
H'00000001 (1): 2.4
H'00000002 (2): 4.8
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
H'00000007 (7): 7
H'00000008 (8): 8
H'00000001 (1): 1
H'00000002 (2): 2
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
H'00000000 to H'00000063 (0 to 99)
H'00000000 (0): OFF
H'00000001 (1): RUN
H'00000002 (2): STOP
H'00000003 (3): RUN/STOP
H'00000004 (4): 100% AT execute/cancel
H'00000005 (5): 40% AT execute/cancel
H'00000006 (6): Alarm latch cancel
H'00000007 (7): Auto/manual
H'00000008 (8): Monitor/setting item
H'00000009 (9): Bank change
H'00000000 (0): Disable
H'00000001 (1): PV/SP/Bank No.
H'00000002 (2): PV/SP/MV
H'00000003 (3): PV/SP/soak time remain
H'00000004 (4): Proportional band (P)
H'00000005 (5): Integral time (I)
H'00000006 (6): Derivative time (D)
H'00000007 (7): Alarm value 1
H'00000008 (8): Alarm value upper limit 1
H'00000009 (9): Alarm value lower limit 1
H'0000000A (10): Alarm value 2
H'0000000B (11): Alarm value upper limit 2
H'0000000C (12): Alarm value lower limit 2
H'0000000D (13): Alarm value 3
H'0000000E (14): Alarm value upper limit 3
H'0000000F (15): Alarm value lower limit 3
H'000000010 (16): Bank No.
Level
Advanced
function
setting
Communi-
cations
setting
Advanced
function
setting

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-hE5an-h

Table of Contents