Omron E5CN-H Communications Manual page 52

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

Variable
Address
Parameter name
type
C1 (81)
0000
Operation/Adjustment Protect
C1 (81)
0001
Initial Setting/Communications Protect
C1 (81)
0002
Setting Change Protect
C1 (81)
0003
Set Point (See note 1.)
C1 (81)
0004
Alarm Value 1 (See note 1.)
Alarm Value Upper Limit 1 (See note 1.) H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
C1 (81)
0005
Alarm Value Lower Limit 1(See note 1.) H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
C1 (81)
0006
C1 (81)
0007
Alarm Value 2 (See note 1.)
Alarm Value Upper Limit 2 (See note 1.) H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
C1 (81)
0008
Alarm Value Lower Limit 2 (See note 1.) H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
C1 (81)
0009
C1 (81)
000A
Alarm Value 3 (See notes 1 and 2.)
C1 (81)
000B
Alarm Value Upper Limit 3
(See notes 1 and 2.)
C1 (81)
000C
Alarm Value Lower Limit 3
(See notes 1 and 2.)
C1 (81)
000D
Heater Burnout Detection 1
C1 (81)
0012
Temperature Input Shift
C1 (81)
0013
Upper Limit Temperature Input Shift
Value
C1 (81)
0014
Lower Limit Temperature Input Shift
Value
C1 (81)
0015
Proportional Band (See note 3.)
C1 (81)
0016
Integral Time (See note 3.)
C1 (81)
0017
Derivative Time (See note 3.)
C1 (81)
0018
Cooling Coefficient (See note 3.)
C1 (81)
0019
Dead Band
C1 (81)
001A
Manual Reset Value
C1 (81)
001B
Hysteresis (Heating)
C1 (81)
001C
Hysteresis (Cooling)
C1 (81)
001D
Heater Burnout Detection 2
C1 (81)
001E
HS Alarm 1
C1 (81)
001F
HS Alarm 2
C1 (81)
0020
Soak Time (See note 1.)
C1 (81)
0021
Wait Band (See note 1.)
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm occurrences
via the status data.
Note 1:
The parameter for the currently selected bank will be accessed.
Note 2:
Not displayed on the Controller display when Alarm 3 is not assigned to an output.
Note 3:
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently selected PID
set is fixed at PID1.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0): No restrictions in operation and adjustment levels
H'00000001 (1): Move to adjustment level is prohibited.
H'00000002 (2): Display and change of only "PV" and "PV/SP" parame-
ters is allowed.
H'00000003 (3): Display of only "PV" and "PV/SP" parameters is allowed.
H'00000000 (0): Move to initial setting/communications setting level is
allowed. (Move to advanced function setting level is dis-
played.)
H'00000001 (1): Move to initial setting/communications setting level is
allowed. (Move to advanced function setting level is not
displayed.)
H'00000002 (2): Move to initial setting/communications setting level is
prohibited.
H'00000000 (0): OFF (Changing of setup on Controller display is allowed.)
H'00000001 (1): ON (Changing of setup on Controller display is prohib-
ited.)
SP lower limit to SP upper limit
H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
H'FFFFB1E1 to H'00007E90 ( − 19999 to 32400)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'FFFFB1E1 to H'00007E90 ( − 199.99 to 324.00)
H'FFFFB1E1 to H'00007E90 ( − 199.99 to 324.00)
H'FFFFB1E1 to H'00007E90 ( − 199.99 to 324.00)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
Standard, heating/cooling, positional proportional (closed):
H'00000000 to H'00007E90 (0.0 to 3240.0)
Positional proportional (floating):
H'00000001 to H'00007E90 (0.1 to 3240.0)
H'00000000 to H'00007E90 (0.0 to 3240.0)
H'00000001 to H'0000270F (0.01 to 99.99)
Temperature: H'FFFFB1E1 to H'00007E90 ( − 1999.9 to 3240.0)
Analog: H'FFFFF831 to H'0000270F ( − 199.9 to 999.9)
H'00000000 to H'000003E8 (0.0 to 100.0)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'0000270F (0 to 9999)
H'00000000(0): OFF
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
Level
Protect
Operation
Adjustment
3-3