Omron E5CN-H Communications Manual page 104

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

Address
Parameter name
Four-byte
Two-byte
mode
mode
0500
2500
Operation/Adjustment Protect
0502
2501
Initial Setting/Communications
Protect
0504
2502
Setting Change Protect
0506
2503
PF Key Protect
0508
2504
Move to Protect Level
050A
2505
Password to Move to Protect
Level
050C
2506
Parameter Mask Enable
0600
2600
Manual MV
0602
2601
Set Point (See note 1.)
0604
2602
Remote SP Monitor
0608
2604
Heater Current 1 Value Monitor
060A
2605
MV Monitor (Heating)
060C
2606
MV Monitor (Cooling)
060E
2607
Valve Opening Monitor
0700
2700
Cooling Coefficient (See note 2.) H'00000001 to H'0000270F (0.01 to 99.99)
0708
2704
Dead Band
070A
2705
Manual Reset Value
070C
2706
Hysteresis (Heating)
070E
2707
Hysteresis (Cooling)
0710
2708
Control Period (Heating)
0712
2709
Control Period (Cooling)
0714
270A
Position Proportional Dead
Band
0716
270B
Open/Close Hysteresis
0718
270C
SP Ramp Time Unit
071A
270D
SP Ramp Set Value
(See note 1.)
071E
270F
MV at Stop
Note 1:
The parameter for the currently selected bank will be accessed.
Note 2:
The parameter for the currently selected PID set will be accessed. For setup area 1, however, the currently selected PID
set is fixed at PID1.
6.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0): No restrictions in operation and adjustment levels
H'00000001 (1): Move to adjustment level is prohibited.
H'00000002 (2): Display and change of only "PV" and "PV/SP" parameters is
allowed.
H'00000003 (3): Display of only "PV" and "PV/SP" parameters is allowed.
H'00000000 (0): Move to initial setting/communications setting level is allowed.
(Move to advanced function setting level is displayed.)
H'00000001 (1): Move to initial setting/communications setting level is allowed.
(Move to advanced function setting level is not displayed.)
H'00000002 (2): Move to initial setting/communications setting level is prohib-
ited.
H'00000000 (0): OFF (Changing of setup on controller display is allowed.)
H'00000001 (1): ON (Changing of setup on controller display is prohibited.)
H'00000000 (0): OFF
H'00000001 (1): ON
H'FFFFF831 to H'0000270F ( − 1999 to 9999)
H'FFFFF831 to H'0000270F ( − 1999 to 9999)
(Can only be set. The monitor value is always H'00000000.)
H'00000000 (0): OFF
H'00000001 (1): ON
Standard: H'FFFFFFCE to H'0000041A ( − 5.0 to 105.0)
Heating/cooling: H'FFFFFBE6 to H'0000041A ( − 105.0 to 105.0)
Position proportional (Closed and direct setting of position proportional MV
ON): H'FFFFFFCE to H'0000041A ( − 5.0 to 105.0)
SP lower limit to SP upper limit
Remote SP lower limit to Remote SP upper limit
H'00000000 to H'00000226 (0.0 to 55.0)
Standard: H'FFFFFFCE to H'0000041A ( − 5.0 to 105.0)
Heating and cooling: H'00000000 to H'0000041A (0.0 to 105.0)
H'00000000 to H'0000041A (0.0 to 105.0)
H'FFFFFF9C to H'0000044C ( − 10.0 to 110.0)
Temperature: H'FFFFB1E1 to H'00007E90 ( − 1999.9 to 3240.0)
Analog: H'FFFFF831 to H'0000270F ( − 199.9 to 999.9)
H'00000000 to H'000003E8 (0.0 to 100.0)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.1 to 999.9)
H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
H'00000001 to H'00000064 (0.1 to 10.0)
H'00000001 to H'000000C8 (0.1 to 20.0)
H'00000000 (0): EU/second
H'00000001 (1): EU/minute
H'00000002 (2): EU/hour
H'00000000 (0): OFF
H'00000001 to H'00007E90 (1 to 32400)
Standard: H'FFFFFFCE to H'0000041A ( − 5.0 to 105.0)
Heating/cooling: H'FFFFFBE6 to H'0000041A ( − 105.0 to 105.0)
Position proportional (Floating or direct setting of position proportional MV
OFF): H'FFFFFFFF to H'00000001 ( − 1 to 1)
Position proportional (Closed and direct setting of position proportional MV
ON): H'FFFFFFCE to H'0000041A ( − 5.0 to 105.0)
Level
Protect
Manual
Control
Operation
Adjustment
Initial
setting
Adjustment
Advanced
function
setting
Adjustment
6-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5en-hE5an-h

Table of Contents