Omron E5CN-H Communications Manual page 46

Digital controllers
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

Note:
When the auto/manual mode is switched with an operation
command through communications and the Controller is in RAM
write mode, the auto/manual status is not stored in EEPROM.
Consequently, if the Controller is restar ted by performing a
software reset or turning the power OFF and ON again, the auto/
manual mode is set to the last saved status.
◆ Switching to Manual Mode during Auto-tuning
If the mode is switched during auto-tuning (AT), the AT will be
cancelled and the Controller will be switched to manual mode.
● Parameter Initialization
The present settings are returned to the default values and written to
EEPROM. This command can be accepted in setup area 1 only. When
this command is issued in setup area 0, an "operation error" will be
generated.
Related
information
00
Default initialization values (See SECTION 3 Communica-
tions Data for CompoWay/F and SYSWAY for details.)
(These settings are the same as the ones used when
"FACT" is selected for the setting data's set value initial-
ization.)
● Alarm Latch Cancel
The applicable alarm latch can be cleared with the related information
setting. The setting can be accepted in both setup area 0 and setup
area 1. An operation error will occur if communications writing is
disabled or if an EEPROM error occurs.
● SP Mode
Select local or remote SP mode with the related information setting.
The setting can be accepted in both setup area 0 and setup area 1. An
operation error will occur in the following situations.
• When AT is being executed
• When the SP Mode parameter is disabled (not displayed at the
Controller)
• When an SP mode change is set for the event input
● Invert Direct/Reverse Operation
Inverting or not inverting direct/reverse operation can be selected with
the related information setting. The setting can be accepted in both
setup area 0 and setup area 1. The related information specifications
are written to EEPROM according to the write mode settings. An
operation error will occur in the following situations: