Command
Command content
code
09
Auto/Manual Switch
0B
Parameter Initialization
0C
Alarm Latch Cancel
0D
SP Mode
0E
Invert Direct/Reverse
Operation
11
Program Start
12
Infrared Communication
Use
(2) Response Code
Normal Completion
Response code
0000
Normal completion
Error Occurred
Response code
Error name
1001
Command too long
1002
Command too short
1100
Parameter error
2203
Operation error
2.3 Detailed Description of the Services
Related Information
00: Automatic mode
01: Manual mode
00: Initialize to defaults
00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: OC alarm latch cancel
0F: All alarm latch cancel
00: Local SP Mode
01: Remote SP Mode
00: Not invert
01: Invert
00: Reset
01: Start
00: OFF
01: ON
Name
Description
No errors were found.
Cause
The command is too long.
The command is too short.
Command code and related
information are wrong.
• The Communications Writ-
ing parameter is set to "OFF"
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
• Processing could not be per-
formed. For details, see (3)
Operation Commands and
Precautions below.
• EEPROM error