Calibrating Sensors - Samson TROVIS 5433 Mounting And Operating Instructions

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

Start-up
2.4

Calibrating sensors

The connected sensors are calibrated in configuration level CO-SYS.
The following applies:
4
CO-SYS -> F02 - 1: Pt 1000 sensors (default)
4
CO-SYS -> F02 - 0: PTC sensors
The resistance values of the sensors can be found on page 91.
If the temperature values displayed on the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sen-
sor, the currently displayed sensor value must be changed to match a temperature (reference
value) measured directly at the point of measurement.
Activate the sensor calibration in CO-SYS over function block F08.
An incorrect sensor calibration can be deleted by setting F08 - 0.
Proceed as follows:
Turn rotary switch "Configuration and parameterization" to COPA.
Display shows: 0 , NR blinks.
q
Set valid key number.
Confirm key number.
Display shows: PA 1
q
Select configuration level CO-SYS.
Open configuration level CO-SYS.
q
Select function block F08.
Activate editing mode for function block F08.
q
Activate function block F08 (F08 - 1).
Confirm function block settings.
q
Select sensor icon:
22
EB 5433 EN
Room sensor RS
Outdoor sensor AS