Samson TROVIS 5433 Mounting And Operating Instructions page 53

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

Functions
Storage sensor SS1
Storage sensor SS2
Flow sensor VS2
Parameter
DHW temperature set point
Parameters
Min. DHW temperature*
Max. DHW temperature*
Hysteresis**
Charging temperature boost***
Stop charging
Storage tank charging pump OFF
Max. charging temperature
Sustained DHW temperature
*
Parameters serve as limitation of the adjustment range for the DHW temp. to be set at the rotary switch
** Deactivation value T = DHW temperature + hysteresis
*** Charging temperature T = DHW temperature + charging temperature boost
WE
Configuration
1
CO2 -> F01 - 1
1
CO2 -> F02 - 1
0
CO2 -> F03
WE
Rotary switch / Range of values
55 °C
Min. to max. DHW temperature
WE
Parameter level / Range of values
40 °C
PA2 / 20 to 90 °C
60 °C
PA2 / 20 to 90 °C
5 °C
PA2 / 0 to 30 °C
10 °C
PA2 / 0 to 30 °C
53 °C
PA2 / 20 to 90 °C
53 °C
PA2 / 20 to 90 °C (only Anl 3 with VS2)
80 °C
PA2 / 20 to 120 °C (only Anl 3 with VS2)
40 °C
PA2 / 20 to 90 °C
Functions of the DHW circuit
EB 5433 EN
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents