Manual operation
Switch to manual operating mode to access all outputs (see wiring diagram in section 11).
When manual operation is activated using the rotary switch for "Operating modes", the ro-
tary switch "Configuration and parameterization" should be in position INFO, otherwise the
pump level cannot be accessed over the rotary pushbutton.
Proceed as follows:
Turn rotary switch "Configuration and parameterization" to INFO.
Turn "Operating modes" switch to +, 0 or –.
Display shows:
q
Select pump level PU.
Open pump level PU.
Display shows: PU 1 - 0 / PU 1 - 1: heating circulation pump switched off/on
q
Select pump:
PU 1: Heating circulation pump UP
PU 2: Exchanger charging pump TLP
PU 3: Storage tank charging pump SLP (DHW valve opens / Anl 5)
PU 4: Circulation pump ZP
PU 5: Binary output BA
Confirm selection. PU blinks.
q
Activate/ deactivate output:
PU _ - 0: deactivate pump/binary output
PU _ - 1: activate pump/binary output
Confirm edited settings.
The modified values remain active as long as the controller is in the manual mode.
q
Select End .
Exit pump level PU.
Turn bottom rotary switch to the desired operating mode.
Note!
Setting the rotary switch to position "Manual operation" (+ 0 –) also sets PU1 - 1 (not in sys-
tem Anl 6). All other outputs are deactivated.
(ZP / Anl 5)
(DHW valve closes / Anl 5)
(TLP / Anl 5)
Manual operation