Samson TROVIS 5433 Mounting And Operating Instructions page 86

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

Appendix
Parameter designation
Display
Range of values (default)
4-point characteristic
Point 1: Outdoor temperature
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
–30 to 50 °C
(point 1: –15 °C, point 2: –5 °C, point 3: 5 °C, point 4: 15 °C)
Only with CO1 -> F04 - 1 and CO1 -> F07 - 1.
4-point characteristic
Point 1: flow temperature
Flow temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
20 to 130 °C
(point 1: 70 °C, point 2: 55 °C, point 3: 40 °C, point 4: 25 °C)
.
Only with CO1 -> F04 - 1 and CO1 -> F07 - 1
4-point characteristic
Point 1: Return flow temperature
Reduced flow temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.
20 to 90 °C (points 1 to 4: 65 °C)
Only with
CO1 -> F04 - 1 and CO1 -> F07 - 1 and CO-SYS -> F01 - 1.
4-point characteristic
Set-back difference at point 2
Set-back difference at point 3 is marked by a square below the
number 3.
0 to 50 °C (points 2 to 3: 15 °C)
Only with CO1 -> F04 - 1 and CO1 -> F07 - 1.
86
EB 5433 EN