after the last phase without an operating fault appearing. Err 6 indicates that the flow tem-
perature deviated from the set point by more than 5 °C for longer than 30 minutes which
leads to the drying process being canceled. While Err 6 appears, a flow temperature of 25
°C is used. Any disconnection of the power supply automatically leads to the drying process
starting from the beginning again.
Note!
In the information level, an active drying function is indicated by the
numbers 2 and 3, storage charging is not performed while the drying of jointless floors is ac-
tive, provided they do not serve to the frost protection of the storage tank.
After the drying function has been successfully completed, the function block CO1 -> F09
should not be deactivated if you want to trace back with which operating parameters the
drying process was carried out.
Function
Drying of jointless floors
5.4

Outdoor temperature dependent deactivation

5.4.1 OT deactivation value rated operation

If the outdoor temperature exceeds the limit in OT deactivation value rated operation , the
heating circuit is put out of service immediately. The valve is closed and the pump is switched
off after the adjusted Lag time of heating circulation pump has elapsed. When the outdoor
The digit behind START _ indicates in which operating
phase the drying of jointless floors is in:
4
1 = Temperature build-up phase
4
2 = Temperature maintaining phase
4
3 = Temperature reducing phase
The drying process has been successfully completed when
the additional icon in the flow temperature display goes out
WE
0
5.0 °C/24 h
45 °C
4 days
5.0 °C/24 h
STOP 0
Functions of the heating circuit
Configuration
CO1 -> F09 - 1
Temperature rise / 1.0 to 10.0 °C/24 h
Maximum temperature / 25 to 60 °C
Maintaining time for maximum temperature /
1 to 10 days
Temperature reduction / 0.0 to 10.0 °C/24 h
START 1
icon. In system code
41
EB 5433 EN