Floating Switch; Optimization; Advance Heating Depending On Outdoor Temperature - Samson TROVIS 5433 Mounting And Operating Instructions

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

When the room sensor is activated and the remote room controller (room panel) is connected
and activated, the measured room temperature is displayed. Nevertheless, it is not used for
control unless the Optimization or Flash adaptation functions have been activated.
Function
Room sensor RS
Note!
The Day set point adjusted via the rotary switch remains unaffected by set point corrections
performed over the room panel. Only the calculated flow temperature set point or the room
temperature set point (for flash adaptation) are adjusted accordingly.

5.6.2 Floating switch

The heating circuit can be switched to night mode by closing the switching contact if a float-
ing switch is connected to input RS.
Function
Room sensor RS
5.7

Optimization

5.7.1 Advance heating depending on outdoor temperature

The controller activates rated operation of the heating system before the time-of-use starts de-
pending on the outdoor temperature. The Advance heating time refers to an outdoor temper-
ature of –12 °C. In case of higher outdoor temperatures, the advance heating time is
reduced.
This means, the colder it is outside, the earlier the night set-back is terminated to ensure that
the desired room temperature Day set point has been reached at the beginning of the
time-of-use, if possible.
Functions
Optimization
Outdoor temperature t
WE
0
WE
0
WE
0
120 min
1
A
Configuration
CO1 -> F01 - 1, option: 1
Configuration
CO1 -> F01 - 0
Configuration
CO1 -> F02 - 1, option: 1
Advance heating time / 0 to 360 min
CO1 -> F07 - 1
Functions of the heating circuit
EB 5433 EN
45