Start-Up; Setting The System Code Number - Samson TROVIS 5433 Mounting And Operating Instructions

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

Start-up

2
Start-up
The modifications of the controller configuration and parameter settings described in this sec-
tion can only be carried out after the valid key number has been entered.
The valid key number for initial start-up can be found on page 96. To avoid unauthorized
use of the key number, remove the page or make the key number unreadable.
2.1

Setting the system code number

Six different hydraulic schemes are available. Each system configuration is represented by a
system code number. The different schemes are dealt with in section 4. Available controller
functions are described in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default
values. Function block parameters and parameter level settings remain unchanged.
The system code number is set in the configuration level.
Proceed as follows:
Turn rotary switch "Configuration and parameterization" to COPA.
Display shows: 0 , NR blinks.
q
Set valid key number.
Confirm key number.
Display shows: PA 1
q
Select Anl .
View current system code number.
Activate editing mode for system code number.
Anl blinks.
q
Set system code number.
Confirm system code number.
Display shows: End
Exit data point "System code number".
Return rotary switch "Configuration and parameterization" to INFO. Display shows: time
18
EB 5433 EN