Samson TROVIS 5433 Mounting And Operating Instructions page 66

Automation system trovis 5400 heating and district heating controller
Hide thumbs Also See for TROVIS 5433:
Table of Contents

Advertisement

System-wide functions
Primary controller:
Functions
Outdoor temperature t
Outdoor temperature 0 to 10 V at input UE
External demand, request
External demand, processing
Forward outdoor temperature, 0 to 10 V
Secondary controller:
Functions
Outdoor temperature t
Outdoor temperature 0 to 10 V at input UE
External demand, request
External demand, processing
Primary controller without outdoor sensor:
The controller is configured for demand-driven heat exchanger control with control of the
feeder pump. Operation of the feeder pump and heat exchanger control are exclusively re-
leased by the received demand signal, not over a time schedule. Demand signals between
1 V and 10 V activate the feeder pump and cause the requested flow temperature (at least
20 °C to 120 °C) plus the adjusted Boost to be adjusted. Demand signals below 1 V are not
processed; they cause the primary valve to be closed and deactivate the feeder pump with a
certain delay. The deactivation delay for the feeder pump can be adjusted.
66
EB 5433 EN
A
A
WE
Configuration
1
CO1 -> F07 - 1
0
CO1 -> F08 - 0
0
CO-SYS -> F10 - 0
0
CO-SYS -> F11 - 1
0 °C
Boost / 0 to 30 °C
0
CO-SYS -> F12 - 1
WE
Configuration
1
CO1 -> F07 - 1
0
CO1 -> F08 - 1
0
CO-SYS -> F10 - 1
70 °C
Requested value / 20 to 90 °C
0
CO-SYS -> F11 - 0