Start-up
2.4

Calibrating the sensors

The connected sensors are calibrated in configuration level CO5.
The following applies:
4
CO5 -> F01 - 1 and CO5 -> F02 - 0: Pt 1000 (Pt 100) sensors (default setting)
4
CO5 -> F01 - 0 and CO5 -> F02 - 0: PTC (Pt 100) sensors
4
CO5 -> F01 - 0 and CO5 -> F02 - 1: NTC (Pt 100) sensors
4
CO5 -> F01 - 1 and CO5 -> F02 - 1: Ni 1000 (Pt 100) sensors
The resistance values of the sensors can be found on page 122.
If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sen-
sor, the currently displayed sensor value must be changed such that it corresponds with a
temperature value (reference value) measured directly at the point of measurement.
Sensor calibration is to be activated in CO5 via function block F20.
An improper sensor calibration can be deleted by setting F20 - 0.
Proceed as follows:
Switch to configuration and parameter level. Display shows: 0 0 0 0
q
Set valid key number.
Confirm key number. Display shows: PA1
q
Select configuration level CO5.
Open configuration level CO5.
q
Select function block F20.
Activate editing mode for function block F20.
q
Select appropriate sensor icon:
Room sensor RF, heating circuits 1, 2
Outdoor sensor AF1
Flow sensor VF, heating circuits 1, 2
Flow sensor VF1, primary heat exchanger circuit
Flow sensor VF2, DHW circuit
Solar collector sensor VF3
26