Functions of the DHW circuit
6.3
DHW heating in the instantaneous water system
TLP
Fig. 9 · Schematics of a system with instantaneous water heater
DHW heating in a system with an instantaneous water heater can be configured using sys-
tem Anl 5.
A hydraulic pressure switch signals the controller the beginning and end of DHW tapping.
When the pressure switch makes contact, the exchanger charging pump starts operation and
DHW temperature control at sensor VS2 is activated.
When the contact is open, the control valve shuts off the DHW circuit. The exchanger charg-
ing pump is deactivated with a certain delay.
Note!
Control of the exchanger charging pump is only possible if the Fault alarm output BA func-
tion has been deactivated.
Functions
Instantaneous heating system with hydraulic
pressure switch
Fault alarm output BA
Parameter
DHW temperature set point
54
EB 5433 EN
WW
VS2
ZP
KW
FDS
TLP
VS2
FDS
ZP
WW
KW
WE
Configuration
0
CO2 -> F14 - 1
2.0
K
(proportional gain) / 0.1 to 50.0
P
120 sec
T
(reset time) / 0 to 999 sec
N
0 sec
d component / 0 to 999 sec
1.0
K
T
(d component of the proportional
P
V
gain) / 0.1 to 10.0
T
(valve transit time) / 10 to 240 sec
45 sec
Y
1
CO-SYS -> F13 - 0
WE
Rotary switch / Range of values
55 °C
Min. to max. DHW temperature
Exchanger charging pump
Flow sensor
Hydraulic pressure switch
Circulation pump
Warm water
Cold water