CO-SYS: General functions (all systems)
F Function
01 Return flow sensor
RüS
02 Sensor selection
03 Summer time/
winter time
changeover
04 Locking the manual
level
05 Control mode
06 Limit deviation for
OPEN signal
07 Release continuous
signal for heating
circuit
08 Sensor calibration
09 Default parameter
values
82
EB 5433 EN
Comment
WE Anl
Function block parameters / Range of values (default)
1
All
CO-SYS -> F01 - 1: Return flow temperature limitation active;
Function block parameter:
Limiting factor / 0.1 to 10.0 (1.0)
Function block cannot be selected if CO2 -> F08 - 1
1
All
CO-SYS -> F02 - 1: Pt1000 sensors
CO-SYS -> F02 - 0: PTC sensors
1
All
CO-SYS -> F03 - 1: Automatic changeover
0
All
CO-SYS -> F04 - 1: Manual level locked;
automatic mode applies in switch positions –, 0, +
1
All
CO-SYS -> F05 - 1: Three-step control
Function block parameters:
K
(proportional gain) / 0.1 to 50 (2.0)
P
T
(reset time) / 0 to 999 sec (120 sec)
N
T
(valve transit time) / 10 to 240 sec (45 sec)
Y
CO-SYS -> F05 - 0: On/off control
Function block parameters:
Hysteresis / 2 to 10 °C (5 °C)
Min. ON time / 0 to 600 sec (120 sec)
Min. OFF time / 0 to 600 sec (120 sec)
0
All
CO-SYS -> F06 - 1 only with CO-SYS -> F05 - 1
Function block parameter:
Max. deviation / 2 to 10 °C (2 °C)
0
All
CO-SYS -> F07 - 1 only with CO-SYS -> F05 - 1;
continuous signal only for actuator with limit switch control
0
All
CO-SYS -> F08 - 1: Measured values of all connected sensors can
be calibrated
0
All
CO-SYS -> F09 - 1: All parameters are reset to their default
values (WE)