Viessmann VITOCAL 300-A Installation And Service Instructions Manual page 168

Type awc-i-m, aw-o-m compact heat pump with electric drive, 230 v~
Table of Contents

Advertisement

Connection and wiring diagrams
Overview of the PCBs and connection options
Message and safety connections at PCB 1 (cross connect PCB)
Pos. Function
q¢Q
ON/OFF switch
q¢W
External blocking, mixer
CLOSED
q¢E
External demand to the
heat pump; mixer OPEN;
operating mode change-
over
q¢R
Fault message, lag heat
source
q¢T
Jumper in safety chain
q¢Z
Power-OFF
q¢U
Jumper fitted at the fac-
tory
q¢I
Appliance fuse F1 ( 6.3 A
(slow))
qYP
Phase switched
168
Explanation
Zero volt contact:
&
Closed: Block enabled
&
Open: No blocking
&
Breaking capacity 230 V,
0.1 A
On-site connection
Zero volt contact:
&
Closed: Requirement
&
Open: No requirement
&
Breaking capacity 230 V,
0.1 A
On-site connection
Zero volt contact:
&
Closed: No fault
&
Open: Fault
&
Breaking capacity 230 V,
0.1 A
Connection on site; remove
jumper when connecting
Zero volt contact:
&
Closed: No blocking (safety
chain has continuity)
&
Open: Block enabled
&
Breaking capacity 230 V,
0.5 A
Connection on site; remove
jumper when connecting
(cont.)
Terminals
1X2.2
1X2.3
1X3.16
1X3.17
1X3.2
1X3.14
or to exter-
nal exten-
sion H1
1X3.13
1X3.12
or to exter-
nal exten-
sion H1
1X3.11
1X3.10
1X3.8
1X3.9
1X3.7
1X3.6
1X3.3
1X3.4
1X3.1

Advertisement

Table of Contents
loading

Table of Contents