Viessmann VITOCAL 300-A Installation And Service Instructions Manual page 127

Type awc-i-m, aw-o-m compact heat pump with electric drive, 230 v~
Table of Contents

Advertisement

Control unit diagnostics
6. "ÓH"
for hours run by the heat
pump in a particular load
situation. See table
"Hours run according to
load classes"
Displays
Display
Description
I (—)
The last 4 digits designate the version of the hardware and soft-
ware of the heat pump module (example: 0000 0000 0000).
Tsh, Tc
Tsh: Set temperature, overheating
(°C)
Tc: Set condensation temperature
Pmop (bar) Max. operating pressure
Ts, Tc (°C)
Ts: Actual suction temperature, overheating
Tc: Actual condensation temperature
Ps (bar)
Actual suction pressure
Pc (bar)
Actual condensation pressure
TI (°C)
Actual LPG temperature
x (%)
Set position of electronic expansion valve
P (%)
Set compressor output
Err (—)
Electronic expansion valve fault.
For explanations see the following table.
Faults at the electronic expansion valve
Display
Err 00: 01000000
Err 00: 02000000
Err 00: 04000000
Err 00: 08000000
Err 00: 10000000
Err 00: 20000000
Further temperatures, pressures and fault messages
Display
Description
tpe
Primary input heat pump 1
tpa
Primary output heat pump 1
tse
Secondary return heat pump 1 and 2
tsa
Secondary flow for heat pump 1
P0
Evaporation pressure heat pump 1 and 2
(cont.)
Description
Suction pressure sensor faulty
Suction gas temperature sensor faulty
Condensation pressure sensor faulty
Condensation temperature sensor faulty
LPG temperature sensor faulty
Stepper motor electronic expansion valve (EEV)
faulty
Troubleshooting
127