Set Flow Temperature For External Demand - Viessmann VITOCAL 300-A Installation And Service Instructions Manual

Type awc-i-m, aw-o-m compact heat pump with electric drive, 230 v~
Table of Contents

Advertisement

Control settings, hydraulics
Screed program
(cont.)
Temperature/time profile 5
A Flow temperature
B Days
Temperature/time profile 7 to 12
Within the temperature/time profiles 7
to 12, the system regulates to the pro-
grammed value (max. flow tempera-
ture) for a period of between 5 and 30
days (see page 162). Delivered condi-
tion 40 °C

Set flow temperature for external demand

The set flow temperature, provided by
the heat pump for external demand, is
set here (see page 137).
Press the following keys:
1. "Device settings".
2. "Programming".
3. "Internal hydraulics".
156
Temperature/time profile 6
A Flow temperature
B Days
Temperature/time
profile
Profile 7
Profile 8
Profile 9
Profile 10
Profile 11
Profile 12
4. y/x for "Set flow ex.
demand" (730C).
5. l/m for the selected value.
6. "BACK"
to confirm.
Delivered condition
Setting range
Duration of
max. flow
temperature
5 days
10 days
15 days
20 days
25 days
30 days
50 °C