5 PARAMETER SETTINGS
Buffer memory address
(hexadecimal)
01D8
Node number and message
H
group of the 1st slave node
01D9
Connection type of the 1st
H
slave node
01DA
Byte module count of the 1st
H
slave node
01DB
Word module count of the 1st
H
slave node
01DC
Double-word module count of
H
the 1st slave node
01DD
Expected packet rate of the 1st
H
slave node
(EXPECTED PACKET RATE)
01DE
Watchdog timeout action of the
H
1st slave node
(WATCHDOG TIMEOUT
ACTION)
01DF
Production inhibit time of the
H
1st slave node
(PRODUCTION INHIBIT
TIME)
01E0
to 01E7
2nd node setting
H
H
01E8
to 01EF
3rd node setting
H
H
01F0
to 01F7
4th node setting
H
H
01F8
to 01FF
5th node setting
H
H
0200
to 0207
6th node setting
H
H
0208
to 020F
7th node setting
H
H
5 - 4
(2)
Description of auto configuration settings
Table 5.1 lists the items that are automatically detected and set with the Auto
Configuration function.
To change the contents of settings, use the sequence program.
Table 5.1 Items set by auto configuration (1/3)
Item
Lower byte: Node number of the 1st slave node (MAC ID) 0
Higher byte: Node that supports 01
group 3, 2 or 1.
Node that supports 02
Node that supports 03
Node that does not support 04
server)
To set a reserved node, specify it with a sequence program.
Selects the connection type of I/O communication.
0001
= Polling
H
0002
= Bit strobe
H
0004
= Change-of-state
H
0008
= Cyclic
H
Lower byte: Input byte module count
Higher byte: Output byte module count
(For a bit module, eight points are calculated as one byte module, and is set in
hexadecimal. Ex.: 0A
for 10 bytes)
H
Lower byte: Input word module count
Higher byte: Output word module count
(set in hexadecimal)
Lower byte: Input double-word module count
Higher byte: Output double-word module count
(set in hexadecimal)
Sets the expected packet rate at a slave node.
Setting value = 0000
(default value)
H
To change the setting value, specify it with a sequence program.
Operation during watchdog timeout at a slave node
Setting value = 0000
timeout (default value) Connection is placed in the
H
timeout state. It will not be recovered until an operator stops
communication and then resumes it.
To change the setting value, specify it with a sequence program.
Sets the production inhibit time.
Setting value = 0000
(default value)
H
To change the setting value, specify it with a sequence program.
Same as the 1st node
Same as the 1st node
Same as the 1st node
Same as the 1st node
Same as the 1st node
Same as the 1st node
MELSEC-Q
Description
to 3F
H
UCMM and uses either message
H
UCMM and uses message group 2.
H
UCMM and uses message group 1.
H
UCMM (group 2 dedicated
H
500 ms
10 ms
(0 to 63)
H