Mitsubishi QJ71DN91 User Manual page 63

Devicenet master-slave module programmable logic controller
Table of Contents

Advertisement

3 SPECIFICATIONS
Buffer memory
3 - 46
(28) Master Function Receive Data (addresses 0700
2047)
The data that was received from each slave node is stored. The data assignment
is shown below. The data is stored in the word boundaries of the slave nodes.
Double-word data is stored in the order of lower word first and higher word next.
If there is an odd number of byte input modules, one byte of empty area will be
inserted for alignment at the word boundary. Bit input modules are treated in the
same way as the byte input modules.
The following shows an example:
<Example>
1st node - Number of byte input modules = 3
Number of word input modules = 3
Number of double-word input modules = 2
2nd node - Number of byte input modules = 1
3rd node - Number of byte input modules = 1
address
0700
2nd byte module
H
0701
Empty
H
0702
1st word module
H
0703
2nd word module
H
Lower word of the
0704
H
1st double-word module
Higher word of
0705
H
the 1st double-word module
Lower word of
0706
H
the 2nd double-word module
Higher word of
0707
H
the 2nd double-word module
0708
H
0709
H
Word input module:
Double-word input module:
Byte input module:
If there in an odd number of
byte input modules, one byte
1st byte module
of empty area will be inserted.
3rd byte module
Input data of the 1st node
1st byte module
Input data of the 2nd node
1st byte module
Input data of the 3rd node
Numeric data represented by bit 9 to 16
Numeric data represented by bit 17 to 32
Data represented by ON/OFF, or numeric data
represented by bit 1 to 8
MELSEC-Q
to 07FF
/1792 to
H
H
3 - 46