Mitsubishi QJ71DN91 User Manual page 32

Devicenet master-slave module programmable logic controller
Table of Contents

Advertisement

3 SPECIFICATIONS
3 - 15
(b) When the auto start is set
1) The module ready (X0F) is turned ON when the power is turned ON,
and the parameter check is executed automatically.
2) If the parameter check is successful, the I/O communication starts and
the I/O communicating (X01) is turned ON. If the parameter check fails,
the master function for error set signal (X03) is turned ON and the ERR.
LED is lit. Check the contents of the error with the "master function for
error information" of the buffer memory address 1B1
POINT
To stop the I/O communication, set Y11, then reset after 200 ms or longer.
When the parameter check is successful:
Module Ready (X0F)
I/O Communicating (X01)
When the parameter check fails:
Module Ready (X0F)
I/O Communicating (X01)
Master Function For Error
Set Signal (X03)
Parameter
check
Parameter
check
MELSEC-Q
.
H
3 - 15