Mitsubishi QJ71LP21 Reference Manual page 376

Q corresponding melsecnet/h network system melsec-q series
Table of Contents

Advertisement

APPENDIX
No.
Name
3
Parameter status of each
SB007C
station
(124)
3
5
Operation status of each
SB0080
station's CPU
(128)
3
CPU RUN status of each
SB0084
station
(132)
3
CPU RUN status of the
SB0085
remote master station
(133)
3
Remote sub-master
SB0086
station CPU RUN status
(134)
3
4
CPU operation status of
SB0088
each station
(136)
3
External power supply
SB008C
information
(140)
3
Module type of each
SB008D
station
(141)
SB0090
Host loop status
(144)
3
SB0091
Forward loop status
(145)
3
Forward loop status of the
SB0092
remote master station
(146)
3: Valid only when SB0047 is off. When it turns on (error), the last data are retained.
4: Minor errors (battery error, etc.) are the type of errors that do not affect the CPU operation.
5: Serious errors (WDT error, etc.) are the type of errors that stop the CPU operation.
Fatal errors (RAM error, etc.) are also the type of errors that stop the CPU operation.
App - 8
Table 1 Special link relay (SB) list (Continued)
Description
Indicates the parameter status of each station. (Not applicable to
reserved stations and the station with the maximum station
number and higher)
Off: No station detected parameter errors
On: A station detected parameter errors
Turns off when the SW007C to SW007F are all "0."
Indicates the operation status of each station's CPU on the PLC-
to-PLC network (including the host station).
Off: All stations normal
On: A moderate or serous error identified
This relay turns off when all of SW0080 to SW0083 are "0."
Indicates the operation status of each remote I/O station on the
remote I/O network (including the host station).
Off: All stations normal
On: Error station identified
This relay turns off when all of SW0080 to SW0083 are "0."
Indicates the CPU RUN status of each station.
Off: All stations are in the RUN or STEP RUN status
On: Stations in the STOP or PAUSE status exist
(including the host)
Turns off when the SW0084 to SW0087 are all "0."
Indicates the CPU run status of remote master station.
Off: Run or STEP RUN status
On: STOP or PAUSE status
Indicates the CPU status of the multiplexed remote sub-master
station.
Off: RUN or STEP RUN status
On: STOP or PAUSE status
Indicates the operation status of each station's CPU or of each
remote I/O station (including the host station).
Off: All stations normal
On: Stations with minor errors exist
Turns off when the SW0088 to SW008B are all "0."
Indicates the information of the external power supply (including
the host).
Off: All stations are without external power supply
On: Stations with external power supply exist
Turns off when the SW008C to SW008F are all "0."
Indicates the module type of each station.
Off: All stations are NET/10 type modules
On: NET/10H type modules exist
Indicates the host's loop status.
Off: Normal
On: Abnormal
Turns off when the SW0090 is all "0."
Indicates the status of stations connected to the forward loop.
Off: All stations normal
On: Faulty stations exist
Turns off when the SW0091 to SW0094 are all "0."
Indicates the status of stations connected to the forward loop.
Off: All stations normal
On: Faulty stations exist
Turns off when the SW0091 to SW0094 are all "0."
MELSEC-Q
Use permitted/prohibited
Remote
Control
Normal
master
station
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
Remote I/O
station
App - 8

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents