7 APPLICATION FUNCTIONS
Write command
Z.REMTO
Write command
ZP.REMTO
Jn
Object network No.
(n1)
Channel number
(n2)
Object number
First address input/output number for object intelligent function module
The upper 3 digits of the 4-digit expression designates the first address input/output
(n3)
number for the intelligent function module mounted to the remote I/O station that is to be
the object.
Write buffer memory first address
(n4)
Designates the first address of the buffer memory for the write destination intelligent
function module.
Write data storage first address device (Host)
(D1)
Designates the host first address device for storing the written data.
(n5)
Number of write data points (word modules)
Write completion device (Host)
Designates the host device to be set to 1 scan on by the write completion.
(D2)
(D2) · · · · · · OFF: Not completed ON: Completed
(D2) + 1 · · · OFF: Normal
1: Bit device · · · · · · · · · · · · · · · · · · X, Y, M, L, F, V, B
2: Word device · · · · · · · · · · · · · · · ·T,C, D, W, ST, R, ZR
3: Word device bit designation · · · · Word device, bit number
7 - 4
2)
REMTO instruction
(Network No. designation)
"Jn"
n1
n2
n3
"Jn"
n1
n2
n3
Description of setting
ON: Abnormal
n4
D1
n5
D2
n4
D1
n5
D2
MELSEC-Q
Z: Executed when on
ZP: Executed when rising
Setting range
1 to 239
1 to 8
1 to 64
0 to FE
H
2
Word device
Constant (K,H)
2
Word device
2
Word device
1 to 960
2
Word device
1
Bit device
Word device bit designation
7 - 4