Error
Code
Error Contents and Cause
*1
(SD0)
At the MELSECNET/MINI auto refresh
network parameter settings, the
module allocation that was set is
2104
different from the actual module
models at the station numbers in the
link system.
There are too many special function
modules that can use dedicated
instructions allocated (number of
modules installed).
(The total of the figures indicated
below is above 1344.)
2105
(AD57(S1)/AD58
(AJ71C24(S3/S6/S8)
(AJ71UC24
(AJ71C21(S1)
(AJ71PT32-S3/AJ71T32-S3
(AJ71QC24(R2,R4)
(AJ71ID1(2)-R4
*: When the expansion mode is used.
*1
Characters in parentheses ( ) indicate the special register numbers where individual information is being
:
stored.
8 - 68
(AD59
modules installed
5)
modules installed
8)
modules installed
10)
modules installed
10)
modules installed
29)
modules installed
125)
modules installed
29)
modules installed
8)
+(AD75
modules installed
12)
total
1344
Corrective Action
Reset the network parameter
MELSECNET/MINI auto refresh unit
module allocation setting so that it
conforms to the station number of the
module that is actually linked.
Reduce the number of special function
modules installed.