Mitsubishi QJ71LP21 Reference Manual page 211

Q corresponding melsecnet/h network system melsec-q series
Table of Contents

Advertisement

7 APPLICATION FUNCTIONS
Error code Error message LED status
3400
REMOTE
PASS. ERR.
3401
REMOTE
PASS. ERR.
7 - 45
(e)
Error codes detected by remote I/O module
ERR. LED:
The remote password file includes
on
incorrect settings.
• The starting I/O No. of the target
module is not included in 0000
0FE0
of the remote I/O station
H
ERR. LED:
The module specified by the starting I/O
on
No. of the remote password file is in the
condition below.
• The module has not been mounted
yet
• QJ71C24 or QJ71E71 intelligent
function module or I/O module
• QJ71C24 and QJ71E71 of function
version A
(f)
Cautions when setting a remote password
1)
If the starting I/O No. is changed after the remote password is set, the
previous remote password set with the Ethernet module/serial
communication module becomes invalid.
2)
Only the remote password set for the directly connected module can
be canceled (unlocked) by remote operation of GX Developer. (The
remote password for the indirectly connected module cannot be
canceled by remote operation.)
Description
to
H
MELSEC-Q
Measures
Correct the starting I/O of the target
module within 0000
to 0FE0
H
remote I/O station.
• Correct the starting I/O to the I/O No.
of the target module.
• Correct the target module to QJ71C24
or QJ71E71.
• Replace the module with QJ71C24 or
QJ71E71 of function version B.
of the
H
7 - 45

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents