6 PROGRAMMING
6 - 9
(b)
CPU module: Refresh parameters
Sets the input/output range for refreshing between the CPU module and
master module.
(c)
Remote I/O module: Intelligent parameter (Initial settings)
Set so that channel 1 is sampling process, channel 2 is 50 times of average
processing, channel 3 is 100 ms of average processing. 1
1 : Note that the number of intelligent function module parameters that
may be set for initial setting is limited.
The number of parameters that may be set for initial setting is as
follows.
Sum total of the numbers of parameters within the setting ranges
of all intelligent function modules
If the number of parameters set exceeds the limited number, the
remote I/O module detects the "SP. PARA ERROR (3301)" error.
POINT
If the remote I/O module has detected the error, read/write the data of the intelligent
function modules using the REMFR/REMTO instruction.
The number of parameters for initial setting is fixed for each intelligent function
module.
To confirm the numbers of parameters for initial setting, refer to the user's manuals
of the corresponding intelligent function modules.
MELSEC-Q
512
1 : The number of Q64AD parameters
for initial setting is 2.
Add this number to all numbers of
parameters of the other intelligent
function modules.