Installation Guidelines - Siemens S5-100U User Manual

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

S5-100U

15.6.1 Installation Guidelines

Installing and Removing the Module
Plug the counter module into a bus unit like other I/Os.
The counter module can only be plugged into slots 0 through 7.
Set the coding key to number 6 on the bus unit.
Installing or Removing the Sensor
Disconnect the 24-V DC power supply (terminals 1 and 2 of the terminal block) before connecting or
disconnecting the sensor cables.
Warning
!
Connecting or disconnecting the 5-V sensor cable while the module is energized can
cause damage to the sensor.
Connection of Pulse and Position Sensors
Connect pulse and position sensors on the front plate by means of a 15-pin sub-D female
connector. The correct cable connectors are listed in Appendix D. The module can supply the
sensors (5 V DC or 24 V DC).
Basically, all sensors can be connected if they fulfill the requirements of the system signals and
supply voltage. Sensors with OPEN-COLLECTOR outputs cannot be connected to the module.
The shield connection of the sensors must be connected to the metallic front connector cover.
Figure 15-8. Pin Assignment of the 15-Pin Sub-D Female Connector
15-20
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
Pin
Assignment
1
5 V Supply voltage
2
5 V Sensor line
3
4
Ground
5
6
Rectangular-wave signal A-N (5 V)
7
Rectangular-wave signal A (5 V)
8
Supply voltage (24 V)
9
Rectangular-wave signal B (5 V)
10
Rectangular-wave signal B-N (5 V)
11
Reference pulse R (5 V)
12
Reference pulse R-N (5 V)
13
Rectangular-wave signal A (24 V)
14
Rectangular-wave signal B (24 V)
15
Reference pulse R (24 V)