Function Modules
Technical Specifications
Address designation
(for ET 100U only)
Number of Inputs
Galvanic isolation
Input voltage
- rated value
- for "0" signal
- for "1" signal
Input current for
"1" signal
Inherent delay
Input frequency
Connection of 2-wire BERO
proximity switches
(24 V DC)
- quiescent current
Length of cable
- unshielded
Outputs
Galvanic isolation
Supply voltage L+
(for load)
- rated value
- permissible range
(including ripple)
Output current
for "1" signal
- rated value
- permissible range
- lamp load
Residual current
at "0" signal
Output voltage
- for "0" signal
- for "1" signal
Short-circuit protection
Fault indication (red LED)
Voltage induced on circuit
interruption (internal)
limited to
Switching frequency
- resistive load
- inductive load
EWA 4NEB 812 6120-02
4DX
2
yes
5 V/24 V DC
0 to 0.8/-33 to 5 V
3 to 5 V/13 to 33 V
typ.
1.5/8.5 mA
typ.
180 µs
max. 500 Hz
possible
1.5 mA
max. 50 m (165 ft.)
2
yes
24 V DC
20 to 30 V
0.5 A
0.5 to 500 mA
max. 5 W
max. 1 mA
max. 3 V
max. L+-2.5 V
electronic
short-circuit
L+-47 V
max. 100 Hz
max. 2 Hz
Total permissible current
of outputs
Driving a digital input
Paralleling of outputs
- max. current
Permissible ambient
temperature for the unit
- horizontal arrangement
- vertical arrangement
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage
(inputs and outputs to
each other and to
;
input to +9 V)
- insulation group
- tested with
Current consumption
- from+9 V (CPU)
typ.
Power loss of the
module
typ.
Weight
approx. 200 g (7 oz.)
S5-100U
1 A
possible
possible
0.5 A
0 to 60 °C (32 to 140 °F)
0 to 40 °C (32 to 104 °F)
100 m (330 ft.)
VDE 0160
60 V AC
1×B
1250 V AC
20 mA
2.5 W
15-13