Siemens S5-100U User Manual page 389

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

S5-100U
Analog Input Module 4 x ± 4 to 20 mA (continued)
Technical specifications
Address designation
(for ET 100U only)
Input ranges
(rated values)
Number of inputs
Galvanic isolation
Input resistance
Connection method
of sensors
Digital representation
of input signal
Measured value
representation
Measuring principle
Conversion principle
Integration time
(adjustable for optimum
noise suppression)
Encoding time
per input
- for 2048 units
- for 4095 units
Permissible voltage
difference
- between inputs
- between inputs and
central ground point
Permissible
input voltage
(destruction limit)
Fault indication for
- range exceeded
- sensor wire break
- general indication of wire
break
EWA 4NEB 812 6120-02
4 AI
±4 to 20 mA
1, 2 or 4
(selectable)
yes (inputs to
grounding point; not
between inputs)
31.25 k
two-wire connection
for 2/4 wire trans-
ducers
12 bits+sign
(2048 units
=rated value)
two's complement
(left-justified)
integrating
voltage-time
conversion
(dual slope)
20 ms at 50 Hz
16.6 ms at 60 Hz
max.
60 ms at 50 Hz
max.
50 ms at 60 Hz
max.
80 ms at 50 Hz
max.
66.6 ms at 60 Hz
max.
±1 V
max.
75 V DC/60 V AC
max.
80 mA
yes (more than
4095 units)
no
no
Noise suppression
for f=nx
(50/60 Hz±1%);
n=1, 2, ...
- common-mode
min.
rejection (V
=1 V)
pp
- series-mode rejection
min.
(peak value of noise
<rated value of
input range)
Basic error limits
Operational error limits
(0 to 60 °C)
(32 to 140 °F)
Single errors
- linearity
- tolerance
Temperature error
- final value
- zero point
Length of cable
- shielded
max.
Supply voltage L+
for 2-wire transducers
- rated value
- ripple V
pp
- permissible range
Connection of com-
pensating box
Insulation rating
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(inputs to +9 V)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
- from L+
typ.
Power loss of the
module
- for 2-wire transducers typ.
- for 4-wire transducers typ.
Weight
approx.
Module Spectrum
(6ES5 464-8ME11)
86 dB
40 dB
±0.15 %
±0.4 %
±0.05 %
±0.05 %
±0.01 %/K
±0.002 %/K
200 m (660 ft.)
24 V DC
3.6 V
20 to 30 V
not possible
VDE 0160
12 V AC
1×B
500 V AC
60 V AC
1×B
500 V AC
70 mA
80 mA
1.0 W
0.7 W
230 g (8 oz.)
14-45

Advertisement

Table of Contents
loading

Table of Contents