Siemens S5-100U User Manual page 362

Simatic s5 programmable controller
Hide thumbs Also See for S5-100U:
Table of Contents

Advertisement

Module Spectrum
Digital Input Module 8 x 24 V DC
L+
1
M
2
.0
.1
.2
.3
.4
.5
.6
.7
DIGITAL INPUT
8 x 24 V DC
6ES5 431-8MA11
1
2
3
4
5
1
3
5
2
4
L+
M
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
14-18
4
3
6
5
8
7
10
9
4
6
+9 V
GND
Data
7
9
6
8
10
Technical Specifications
Address designation
(for ET 100U only)
Number of inputs
Galvanic isolation
- in groups of
Input voltage L+
- rated value
- "0" signal
- "1" signal
Input current at
"1" signal
typ.
Inherent delay
- from "0" to "1"
typ
- from "1" to "0"
typ.
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage
(+ 9 V to
)
- insulation group
- tested with
Rated insulation voltage
(+ 9 V to L+)
- insulation group
- tested with
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Connection of 2-wire
BERO proximity switches
- residual current
Current consumption
- from + 9 V (CPU)
typ.
Power loss of
the module
typ.
Weight
approx.
S5-100U
(6ES5 431-8MA11)
8 DI
8
yes (optocoupler)
8
24 V DC
0 to 5 V
13 to 33 V
8.7 mA
5.5 ms
4 ms
100 m (330 ft.)
VDE 0160
12 V AC
2 x B
500 V AC
30 V AC
2 x B
500 V AC
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
possible
1.5 mA
32 mA
2 W
190 g (6.7 oz.)
EWA 4NEB 812 6120-02