S5-100U
Analog Output Module 2 x 1 to 5 V
L+
1
M
2
QV
4
3
S+
Ch.0
S -
5
6
M ANA
QV
8
7
S+
Ch.1
S -
9
10
M ANA
R 3k
ANALOG OUTPUT
2 x 1 ... 5 V
6ES5 470-8MD12
1 2
3
4
5
0V
- 15V
+15V
1
3
5
2
4
S+ QV
S-
M A S+ QV S- M A
L+
M
Ch.0
EWA 4NEB 812 6120-02a
+
24 V
R
R
6
6
+9 V
GND
Data
7
9
10
6
8
Ch.1
Technical specifications
Address designation
(for ET 100U only)
Output range
(rated values)
Number of outputs
Galvanic isolation
Input resistance
min.
Connection method
Digital representation
of output signal
Measured value
representation
Conversion time
(0 to 100%)
max.
Permissible overload
Short-circuit protection
Short-circuit current
Permissible voltage
difference to central
ground point and
between outputs
max.
Basic error limits
Operating error limits
(0 to 60 °C)
(32 to 140 °F)
Single errors
- linearity
- temperature error
Length of cable
- shielded
max.
Supply voltage L+
- rated value
- ripple V
PP
- permissible range
(ripple included)
Insulation rating
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Rated insulation voltage
(outputs to L+,
between outputs,
output to +9 V)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
- from L+
typ.
Power loss of
the module
typ.
Weight
approx.
Module Spectrum
(6ES5 470-8MD12)
2 AQ
1 to 5 V
2
yes (outputs to
grounding point and
between outputs)
3.3 k
two- or four-wire
connection
11 bits + sign
(1024 units=rated
value)
two's complement
(left-justified)
0.15 ms
25%
yes
±30 mA
75 V DC/60 V AC
±0.2%
±0.06%
±0.2%
±0.01%/K
200 m (660 ft.)
24 V DC
3.6 V
20 to 30 V
VDE 0160
12 V AC
1 x B
500 V AC
60 V AC
1 x B
500 V AC
170 mA
100 mA
3.1 W
290 g (10 oz.)