S5-100U
Digital Input Module 8 x 5 to 24 V DC
.0
.1
.2
.3
.4
.5
.6
.7
1 -
2 -
DIGITAL INPUT
8 x 5 ... 24 V DC
6ES5 433-8MA11
1
2
3
4
S1
4.7 k
1
3
2
4
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
EWA 4NEB 812 6120-02
L+
1
M
2
4
3
6
5
8
7
10
9
L+
M
8
5
6
+9 V
GND
Data
S2
5
7
9
6
8
10
Technical Specifications
Address designation
(for ET 100U only)
Number of inputs
Galvanic isolation
- in groups of
Input voltage L+
- rated value
- "0" signal
- "1" signal
Permissible range
Input resistance
The LED displays
the evaluated signal
Inherent delay
approx.
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage
(+ 9 V to L+)
- insulation group
- tested with
Rated insulation voltage
(+ 9 V to
)
- insulation group
- tested with
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Current consumption
- from + 9 V (CPU)
typ.
- from L+
typ.
Power loss of the
module
typ.
Weight
approx.
* reversible in groups of 8
Module Spectrum
(6ES5 433-8MA11)
8 DI
8
yes (optocoupler)
8
5 to 24 V DC
Vin approx. 25% L+
Vin approx. 45% L+
4.5 to 30 V
4.7 k to L+ or M;
reversible on the back
of the module *
1 ms or 10 ms;
reversible on the back
of the module *
100 m (330 ft.)
VDE 0160
30 V AC
2 x B
500 V AC
12 V AC
2 x B
500 V AC
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
6 mA
60 mA
2.4 W
225 g (8 oz.)