Module Spectrum
Digital Output Module 8×24 V DC/0.5 A
1
2
4
.0
3
.1
6
.2
5
.3
8
.4
7
.5
10
.6
9
.7
DIGITAL OUTPUT
8 x 24 V DC/0.5 A
6ES5 441-8MA11
1 2
3
4
5
C
1
3
5
2
4
L+
M
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
14-24
L+
M
5
6
+9 V
GND
Data
7
9
6
8
10
Technical specifications
Address designation
(for ET 100U only)
Number of outputs
Galvanic isolation
- in groups of
Load voltage L+
- rated value
- permissible range
(including ripple)
- value at t<0.5 s
Warning
!
Capacitor remains loaded
after switch off of L+
Output current for
"1" signal
- rated value
- permissible range
- lamp load
max. 5 W
Residual current at
"0" signal
max. 1.0 mA
Output voltage
- "1" signal
max. L+ (- 1.2 V)
Short-circuit protection
Voltage induced on circuit
interruption (internal) limited to
Switching frequency
- resistive load
max. 100 Hz
- inductive load
max. 2 Hz
Total permissible
current of outputs
Driving of digital input
Paralleling of 2 outputs
- maximum current
Permissible ambient
temperature of PLC
- horizontal arrangement
- vertical arrangement
Length of cable
- unshielded
max. 100 m (330 ft.)
Insulation rating
Rated insulation voltage*
(+9 V to
)
- insulation group
Current consumption
- from +9 V (CPU)
typ.
- from L+(without load)
typ.
Power loss
of the module
typ.
Weight
approx. 220 g (7.7 oz.)
* Relevant only for isolated assembly in the ET 100U
S5-100U
(6ES5 441-8MA11)
8 DQ
8
no
8
24 V DC
20 to 30 V
35 V
0.5 A at 60 °C (140 °F)/
1 A at 30 °C (86 °F)
5 mA to 1 A
none
- 15 V
4 A
possible
possible
0.8 A
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
VDE 0160
12 V AC
1×B
14 mA
15 mA
3.5 W
EWA 4NEB 812 6120-02