Alert Setup

Field Communicator
Configure > Alert Setup (2‐3)
An alert is a notification that the instrument has detected a problem. A shutdown is an action that the instrument
takes to drive the air output to the Zero Power Condition as per figure 3‐3. Some alerts can be configured to shutdown
the instrument. Refer to table 3‐9 for default alert and shutdown settings.
Alerts may be enabled or disabled with the instrument In Service, Out of Service, Protected, or Not Protected.
However, the instrument must be Not Protected to enable or disable a shutdown. Alerts are not processed when a
diagnostic is in progress.
If shutdown is enabled, and the alert is active, the instrument will latch in the shutdown state until power to the
instrument is cycled and the alert has cleared. While in the shutdown condition, HART communication will continue if
the instrument remains powered.
For a detailed explanation of the alerts and the recommended actions, refer to Section 5.
Table 3‐9. Default Alert and Shutdown Settings
ALERT
Travel Sensor Failure
Temperature Sensor Failure
Minor Loop Sensor Failure
Pressure Sensor Failure
Drive Current Failure
Critical NVM Failure
Non-Critical NVM Failure
Flash Integrity Failure
Reference Voltage Failure
Drive Signal Out of Range
(1)
Supply Pressure Low
Travel Deviation
(1)
Pressure Fallback Active
High Travel
Low Travel
High-High Travel
Low-Low Travel
Travel Limit/Cutoff High
Travel Limit/Cutoff Low
Integrator Saturated High
Integrator Saturated Low
Cycle Count High
Travel Accumulator High
Output Circuit Communication Failure
Alert Record Not Empty
Alert Record Full
Instrument Time is Approximate
1. Instrument level AD, PD, or ODV only.
DEFAULT ALERT SETTING
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Configuration
February 2017
DEFAULT SHUTDOWN SETTING
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
Not Available
35

Advertisement

Table of Contents
loading

Table of Contents