Spec Sheet; Edit Instrument Time; Travel/Pressure Control; Travel/Pressure Select - Fisher FIELDVUE DVC6200 Instruction Manual

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

Configuration
February 2017
D Input Range Lo—Permits setting the Input Range Low value. Input Range Low should correspond to Travel Range
Low, if the Zero Power Condition is configured as closed. If the Zero Power Condition is configured as open, Input
Range Low corresponds to Travel Range High. See figure 3‐1.
Figure 3‐1. Calibrated Travel to Analog Input Relationship
TRAVEL
RANGE
HIGH
TRAVEL
RANGE
LOW
INPUT RANGE
LOW
NOTE:
ZPC = ZERO POWER CONDITION
A6531‐1

Spec Sheet

The Spec Sheet provides a means to store the entire control valve specifications on board the DVC6200.

Edit Instrument Time

Permits setting the instrument clock. When alerts are stored in the alert record, the record includes the time and date.
The instrument clock uses a 24‐hour format.

Travel/Pressure Control

Field Communicator
Configure > Manual Setup > Travel/Pressure Control (2‐2-3)

Travel/Pressure Select

This defines the operating mode of the instrument as well as the behavior of the instrument should the travel sensor
fail. There are four choices.
D Travel Control—The instrument is controlling to a target travel. Fallback is not enabled.
D Pressure Control—The instrument is controlling to a target pressure. Fallback is not enabled.
D Fallback-Sensor Failure—The instrument will fallback to pressure control if a travel sensor failure is detected.
18
ZPC = OPEN
ZPC = CLOSED
THE SHAPE OF THESE LINES
DEPENDS ON THE INPUT
CHARACTERISTICS LINEAR
CHARACTERISTIC SHOWN
ANALOG INPUT
mA OR % OF 4‐20 mA
INPUT RANGE
HIGH
Instruction Manual
D103605X012