3.2.9 Loop Break Time/Field Calibration

Figure 3.8 Flow Chart for Loop Break Time/Field Calibration

ENTER LOOP BREAK TIME MENU:
Press a
Press d
Press a
Press d
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press b
Press d
Loop Break is an additional safety feature intended to monitor the rate of change of the
process value, while approaching the SP1. It is strictly intended as an additional warning
system, therefore its use is entirely optional. An active Loop Break will cause the Process
Value digits to blink in a rotating pattern. If the process value reaches the set point the
blinking will stop and B.TIM is completed successfully, otherwise BR.AL Break Alarm
warning will flash, and Output 1 will be turned off.
LOOP BREAK TIME VALUE SUBMENU:
Press d
Press b & c 8) Press b and c buttons to enter a new Loop Value (0 to 99.59).
Press d
Loop Break Time Value allows the user to determine the time interval in MM:SS (from
zero to 99 minutes and 59 seconds) that the Process Value changes at least 10 counts or
if the Input Type is either RTD or Thermocouple, the value changes 4° Fahrenheit or 2°
Celsius. At the specified time interval, if the process value change is less than the stated
rate, flashing B.TIM will be displayed, the output 1 will be de-energized, and Alarm 1
energized. Loop break time will be disabled when the Process Value (PV) enters the
control band.
C.J. READING ADJUST SUBMENU:
Press d
Press b & c 11) Press b and c buttons to enter a new Reading Adjust value
Press d
1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a , if necessary, until Display advances to LOOP Loop
Break Time Menu.
4) Display advances to Loop Break Time ENBL Enable or DSBL
Disable Submenu and flashes the previous selection.
5) Scroll through the available selections: ENBL or DSBL .
6) Display shows STRD stored message momentarily and then
advances to B.TIM Loop Break Time Value Submenu.
7) Display flashes 1 st digit of previous Loop Value.
9) Display shows STRD stored message momentarily and then
advances to R.ADJ Reading Adjust Submenu.
10) Display flashes 1 st digit of previous reading adjust value.
(-1999 to 9999).
12) Display shows STRD stored message momentarily and then
advances to SP.DV Setpoint Deviation Menu.
33
It is required
that you put
the controller
in the Standby Mode
for any configuration
change other than Set
Points & Alarms.