Example 3:
Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, "ALR.H" = 10
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
RED
• --------------- • ------ • ------ • -------------------------------- • ------ • ------- • ----------------
0
190 200 210
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.
If Analog Output Option board is installed (Alarm 1 is disabled), only
Alarm 2 is active and only two colors are available.
Example 4:
Output 1 = Relay, Setpoint 1 = 200
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 Setup: Deviation, Band, "ALR.H" = 20
Alarm 2 Setup: Deviation, Hi/Low, "ALR.H" = 10, "ALR.L" = 5
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display colors change sequences:
AMBER
• -- --------------- • ---------------- • ------------- • -------------- • ------------- • ---------------------
0
180
Reset: The instrument automatically resets after the last menu of
the Configuration Mode has been entered. After the instrument
resets, it advances to the Run Mode.
RED
RED
GREEN
195
RED
290
GREEN
200
210
57
GREEN
300 310
RED
AMBER
220
RED