RESET SETUP SUBMENU:
Press d
Press b & c 34) Press b and c buttons to enter a new "Reset" value.
Press d
RATE SETUP SUBMENU:
Press d
Press b & c 37) Press b and c buttons to enter a new RATE value.
Press d
CYCLE TIME SUBMENU:
Press d
Press b & c 40) Press b and c buttons to enter a new "Cycle Time" value.
Press d
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays'
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).
33) Display flashes 1
35) Display shows STRD stored message momentarily and then
advances to RATE only, if it was changed, otherwise press a to
advance to RATE Rate Setup Submenu.
Reset unit is in seconds 0-3999.
36) Display flashes 1
38) Display shows STRD stored message momentarily and then
advances to the CYCL only, if it was changed, otherwise press a
to advance to CYCL Cycle Time submenu for RTD and
Thermocouple types.
Rate unit is in seconds 000.0-399.9.
If the Output 1 is Analog Option the display skips to Damping
Factor.
39) Display flashes 1
value.
(1 to 199 seconds)
41) Display shows STRD stored message momentarily and then
advances to DPNG only, if it was changed, otherwise press a to
advance to DPNG Damping Factor Submenu.
st
digit of the previous I REST Reset value.
st
digit of previous D RATE Rate value.
st
digit of the previous CYCL Cycle Time
40